Setting the Standard in Photoionization Detection Technology ...

The piD-TECH® eVx family of photoionization detectors offers the latest in technology and upgrades without compromising the award winning features that make the piD-TECH line of sensors the best choice for OEM Manufacturers. Providing better value, design flexibility and lower detection limits. These improvements include greater stability over temperature and humidity changes, integral shielding, improved response time and minimum detection limits down to 0.5 ppb.

These detectors are designed intrinsically safe and with a 4P platform for ease of installation in both portable and fixed gas detection units.  For use in a myriad of VOC (volatile organic compound) monitoring applications including environmental and safety applications in the industrial, commercial or residential markets. 
Unit of Measure
Items
 

10.6 eV Photoionization Sensor

 

10.6 eV Photoionization Sensor

 

10.6 eV Photoionization Sensor

 

10.6 eV Photoionization Sensor

 

10.6 eV Photoionization Sensor
Applications N/A
  • Industrial Hygiene & SafetyMonitoring
  • Confined Space Entry
  • Soil Contamination and Remediation
  • Hazmat Sites & Spills
  • Low Concentration Leak Detection
  • Indoor Air Quality
  • Fenceline Monitoring
  • EPA Method 21
  • Features N/A
  • Designed for use in intrinsically safecircuits: UL, CAN/CSA, ATEX, IECExcertified
  • Integral shielding
  • 4P cell platform compatible
  • Lamp re-Ignition circuit for fast,repeatable and dependable startup
  • Reliable long lamp life: guaranteed6,000 continuous hours
  • Internal, input voltage regulation forgreater signal stability
  • Dual filter technology protects fromaerosols and particulates
  • Negligible temperature response
  • Guard electrode curtails humidityeffects
  • Rapid response & greater baselinestability
  • Easily cleaned and field serviced
  • Out of warranty Sensor ExchangeProgram
  • Color N/A Green N/A Purple N/A Red N/A Yellow N/A Blue
    Range (Isobutylene) N/A 10,000 ppm N/A 2,000 ppm N/A 200 ppm N/A 20 ppm N/A 2 ppm
    Minimum Detectable Quantity (Isobutylene) N/A 500 ppb N/A 100 ppb N/A 10 ppb N/A 1.5 ppb N/A 0.5 ppb
    Image N/A  
    N/A  
    N/A  
    N/A  
    N/A  
    T90 Response Time N/A
    Temperature Range N/A -20 °C to 60 °C (-4 °F to 140 °F)
    Relative Humidity Range N/A 0 to 90% non-condensing
    Humidity Response N/A ≤ 1% at 90% relative humidity
    Humidity Quenching Effect N/A ≤ 15% at 90% relative humidity
    Onboard Filter N/A Removes liquids / particles
    Supply Voltage N/A 3.2 V to 5.5 V (input voltage regulator included)
    Current N/A 24 mA to 36 mA
    Power Consumption N/A 80 mW to 200 mW (dependent upon supply voltage)
    Output Signal N/A 0.045 V to 2.5 V linear
    Weight N/A < 8 grams
    Serviceable Parts N/A Lamp, detector cell, filters (2), cap, spacer
    Warranty Period N/A 18 months
    Patents N/A US Pat 6,646,444; Japan Pat 3,793,757
    Accuracy N/A ± 3% of reading, with constant temperature and
    Lamp Life N/A Guaranteed 6000 continuous hours (typical life significantly longer)
    Approvals N/A USA — UL 913, 8th Edition. Intrinsically Safe Apparatus and Associated Apparatus for use in Class I, Div 1, Groups A, B, C, D locations.
    Europe — ATEX directives: EN 60079-0:2012, A11:2013; EN 60079-11:2012; II 1 G Ex ia IIC T4, -20 °C to 60 °C
    ATEX certificates: DEMKO 13 ATEX 1304446U Rev. 1;    0539
    Other — IECEx Standards: 60079-0 Ed. 6; 60079- 11, Ed. 6; Certificate IECEx UL 13.0050U Issue: 1; CAN/CSA C22.2 No. 157-92

    Our Privacy Policy has changed, and by continuing to use the site, you agree to our new Privacy and Cookie Policy.

    Ok